Technical Reports
Gas Burner Systems - voltage reading
What type of voltage reading should be present at the Fireye test ports?

For a flame rod Fireye system there should be a 14 to 18 VDC signal present at the test ports.

For an UV Fireye system there should be a 4.0 to 6.0 VDC signal present at the test ports.